top of page
  • Nick

Sample calcs: Sizing pull boxes and conduits

Sample calcs are going to be short examples of how to do calculate something that might help you out. They are geared towards issues that have come up in the field. If you are an electrician, you can probably skip this post. This is geared towards an estimate an engineer could use for pricing (aka RSMeans), or review of a schedule. As with all posts, this is for educational use only.


On paper, changing wire schedules is fairly cheap. After that, wiring modifications are far more costly. Typically, signal wiring will come in via hardwire or network cable.


If you are reviewing a conduit schedule, make sure...

  1. AC and DC wires are in separate conduit (as AC will induce waves on the DC)

  2. Signal cables are only in conduit with DC wires

  3. Conduit fill is not excessive (usually 40% by cross sectional area)

  4. Box fill is not excessive

Calculating conduit fill is fairly easy. First, check your local electrical codes! In the USA, this would be Table 9 of the NEC. Roughly, you sum up the cross-sectional area of the wires, divide by 0.4 and round up to the next size for your type of conduit. I recommend you actually go up two sizes or divide by 0.3, just to save time when signals are added later.


Pull box sizing is a little more complex. Table 314.16 goes into details. I attached a little spreadsheet to help out. Please note that this is for educational uses only- you still need to check this against the NEC and verify it yourself! (I did add the notes of where to look for exceptions and additions. Grounded conductors can be key, hence the separate column.)

Let's go ahead and try to size conduits! Imagine you have three conduits coming from three local control panels into a junction box, which then feeds out via on conduit to your PLC cabinet. C-xx will stand for the conduits and JB-yy for the junction box.


C-01 4x 10 AWG THHN ungrounded conductors

1x 12 AWG THHN grounded conductor

C-02 16x 12 AWG THHN ungrounded conductors

3x 14 AWG THHN grounded conductors

C-03 12x 18 AWG TSP ungrounded conductors

1x 14 AWG THHN grounded conductor

JB-01 All wires above

C-04 All wires above


But alas, if you are not an electrician, you probably need some reference.

AWG- American Wire Gauge, basically the size of the copper

THHN- Insulation type, heat resistant thermoplastic for dry and damp applications

TSP- Twisted shielded pair, commonly used for signal wires. Can come with a variety of shields, so we will assume it is sized as TFN for this calculation. (You really want to check this assumption before you get in the field!)


Some other common abbreviations for the controls industry include...

EMT- Conduit type, Electrical Metallic Tubing

FMC- Conduit type, Flexible Metal Conduit

MTW- Insulation type, machine tool wiring, heat resistant thermoplastic. Very flexible, I like to use inside of cabinets when possible, but expensive

THWN- Insulation type, heat resistant thermoplastic for dry and damp applications, slightly cheaper than THHN

UF- Insulation type, underground feeder and branch circuit


The first thing that would strike me is the 18 AWG TSP wire for the ungrounded conductors. Typically, this means you would have a DC signal (perhaps 4-20 mA). You need to check that beforehand, as putting everything in JB-01 would allow for cross talk (the AC wires inducing a voltage on the DC wires) and will certainly do so for C-04.


For the purposes of the demonstration, let's calculate the size of JB-01 and C-04 assuming they are all AC. I will leave coming back to do the same as an exercise for the reader.


We need the cross-sectional area of each of the wires.

THHN 10 AWG 0.0211 in2 13.61 cm2

12 AWG 0.0133 in2 8.581 cm2

14 AWG 0.0097 6.258

TFN 18 AWG 0.0055 3.548


The sum of areas inside would be...

C-01: 4 * 0.0211 + 1 * 0.0133 = 0.0977 in2

C-02: 16 * 0.0133 + 3 * 0.0097 = 0.2419 in2

C-03: 12 * 0.0055 + 1 * 0.0097 = 0.1417 in2

C-04: 0.0977 + 0.2419 + 0.1417 = 0.4813 in2


For more than two wires in a conduit, 40% is a standard fill. Let's assume EMT for the conduit. Going to Chapter 9, you can find Table 4, Article 358 and compare to the minimum areas you calculate with the fill...


C-01: 0.0977 / 0.4 = 0.24425 in2 => 1/2" (metric 16)

C-02: 0.2419 / 0.4 = 0.60475 => 1" (metric 27)

C-03: 0.1417 / 0.4 = 0.35425 => 3/4" (metric 21)

C-04: 0.4813 / 0.4 = 1.20325 => 1 1/4" (metric 35)


While this calculation will do that, I strongly encourage you to oversize any conduit with signal. It is way cheaper to put in an oversized conduit than to add a second one in.


Now, for the junction box size! Check out NEC 314.16. You will note Table 314.16(B) gives volume per conductor.

Size in3 cm3 # in JB1 in3 sum

18 1.50 24.6 12 18

16 1.75 28.7 12 21

14 2.00 32.8 4 8

12 2.25 36.9 17 38.25

10 2.50 41.0 4 40


Simply sum the contributions of each size and you get a 125.25 in3 box, which sounds about right. Five inches per side would make plumbing these conduits in fairly easy.


Note: This is slightly different than what your electrician should do. Grounded and ungrounded connectors do make a difference and you can get a discount on your box. This is outside of our scope but something to be aware of.


Are there shortcuts you could make? Well, if you had wires of the same size, you may be able to make use of the Annex C tables in NEC.


Typically signal wires are oversized, but plentiful. Mistakes don't have to be. Make your own spreadsheet (or modify this one), oversize things to save money in the long run and always double check your calculations!

6 views0 comments

Recent Posts

See All

Pro tips: Process Engineers

Pro tips exist to help you in your career. They usually focus on topics that I have experience with, but I had the pleasure of talking...

Podcasts on automation

It turns out there are good number of relevant podcasts for this field. They are also great for when you are on the road! Just a few...

Comments


bottom of page